Shenzhen Kinda Technology Co., Ltd
Contact Now

Multi Machine Variable Frequency Drive Pump Control Water Supply Energy Saving

Model Number : KD388

Place of Origin : China

Brand Name : Kinda

MOQ : Negotiable

Price : Negotiable

Delivery Time : 3~8 Day

Payment Terms : TT

Supply Ability : Adequate inventory

way of communication : Standard Modbus communication

run : Smooth main/slave switching, no change in water pressure

start up : Simple parameter setting, one-button start automatic addition and subtraction pump control

PCB protection : Spray three anti-paint to protect the circuit board intelligently and efficiently

installation : Simple wiring installation

control : Main/slave control energy saving

Contact Now

Multi-Machine Variable Frequency Drive Pump Controls Constant Pressure Water Supply

When the water supply automatic control system works, the equipment detects the pressure change of the water supply pipe network when the water consumption changes through the high-sensitivity pressure sensor installed on the water supply pipe network, and continuously transmits the changed signal to the inverter, and judges the operation and setting by the microcomputer. After the pressure is compared, the controller sends a command to change the frequency. The controller changes the speed of the pump motor and the number of enabled pumps by changing the frequency, automatically adjusting the water consumption of the peaks and valleys, and ensuring that the pressure of the water supply pipe network is constant to meet the water demand of the user.

1.Wiring connection

Multi Machine Variable Frequency Drive Pump Control Water Supply Energy Saving

Multi Machine Variable Frequency Drive Pump Control Water Supply Energy Saving

2.Parameters setting

Function code Default value Set value Description
F1-11 1 I# inverter 1 1# inverter (master), it must connect the pressure sensor.
2# inverter 2 2# inverter (slave / standby master), connect the pressure senor.
3# inverter 3 3# and 4# inverters (slave).
4# inverter 4 Warning: the address of each inverter cannot be the same, otherwise, the system will work abnormally.
F0-00 1 2 Multiple pumps system
F0-01 0.4MPa Customer set 1. Please set it correctly based on requested pressure, the unit is MPa, 1MPa=10bar.
2. Most of the family used systems, the pressure is 0.3~0.4MPa (3~4bar)
F0-02 80% Customer set Wake up pressure; it is the percentage of F0-01.
F0-03 0 0 It must be set as “0” while use 0~10V remote pressure gauge.
1 It must be set as “1” while use 4~20mA pressure transducer.
F0-04 1.6MPa 1.6MPa 1. To set the maximum measure range of pressure transducer.
2. It must be set correctly, otherwise it may cause pressure is inaccurate.
F0-25 300Min Customer set To set the running time as master pump, when time arrive, it switches to next pump as master.
When set F0-25=0, this pump will only work as slave pump.

3. KD388 is designed to be installed directly on the water pump. The following are multiple online intelligent control constant pressure water supply.

Multi Machine Variable Frequency Drive Pump Control Water Supply Energy Saving


Product Tags:

pump frequency converter

      

vfd pump control

      
Best Multi Machine Variable Frequency Drive Pump Control Water Supply Energy Saving wholesale

Multi Machine Variable Frequency Drive Pump Control Water Supply Energy Saving Images

Inquiry Cart 0
Send your message to this supplier
 
*From:
*To: Shenzhen Kinda Technology Co., Ltd
*Subject:
*Message:
Characters Remaining: (0/3000)